Latest Downloads
-
Crane Fluid Flow Examples in MS ExcelArt Montemayor - Jan 31 2012 08:22 PM
-
Surface Tension of Pure Liquidsankur2061 - Jan 24 2012 02:43 PM
-
Filament Yarn Quench Air Systemankur2061 - Jan 18 2012 05:03 PM
-
Gravity Tank Drainage Calculator for Uniform Cross Sectionsstudent88 - Dec 19 2011 03:16 PM
-
Gravity Tank Drainage Calculator for Hemispherical Cross Sectionsstudent88 - Dec 19 2011 03:14 PM
-
Gravity Tank Drainage Calculator for Cylindrical Cross Sectionsstudent88 - Dec 19 2011 03:13 PM
-
Drainage Between Two Reservoirsstudent88 - Dec 19 2011 03:11 PM
-
Cooling Tower Water Loss CalculatorDB Shah - Dec 19 2011 02:24 PM
-
Equivalent Length Calculations for Pipes and Valvesankur2061 - Nov 17 2011 09:00 AM
-
Slurry Pump Calculation 1.1mramono - Nov 10 2011 05:10 PM
Popular Store Titles
Tank Jacket Calculator
Specification Sheet Collection
PIPESIZE
Relief Valve Sizing
Rupture Disc Sizing
Recent Status Updates
-
Chris HaslegoNew blog entry - Revisiting the Reputation System - http://www.cheresources.com/invision/blog/1/entry-205-revisiting-the-reputation-system/
-
Govind Manglanihey anyone knows how energy is conserved in a petroleum refinery ...i need a overveiw of enery conservation method in major units.Like fcc,reformin,ADU,VDU etc..
Chemical and Process Engineering Resources
Latest Blog Entries
Plate Heat Exchangers: Preliminary Design
Nov 08 2010 06:10 PM | Chris HaslegoShare this topic:
Numerous articles have been published regarding the advantages of compact heat exchangers. Briefly, their higher heat transfer coefficients, compact size, ease of service, cost effectiveness, and their unique ability to handle fouling fluids make compact exchangers a good choice for many services.
Plate Heat Exchanger Parts and Service Do you need parts or service for your plate heat exchanger? Maybe you just have a technical question. Give us a call at (804) 370-3855 or complete the email form below and we'll be happy to help. |
A Quick Look at the Basics
Plate heat exchangers consist of pressed, corrugated metal plates fitted between a thick, carbon steel frame. Each plate flow channel is sealed with a gasket, a weld, or an alternating combination of the two. It is not uncommon for plate and frame heat exchangers to have overall heat transfer coefficient that are 3-4 times those found in shell and tube heat exchangers.
![]() | Eq. (1) |
Specifying a Plate and Frame Heat Exchanger
| Figure 1: Parts Structure for a Plate Heat Exchanger |
Engineers often fail to realize the differences between heat transfer technologies when preparing a specification. This specification is then sent to vendors of different types of heat exchangers. Consider the following example:
A process stream requires C276 material to guard against corrosion. The stream needs to be cooled with cooling water before being sent to storage. The metallurgy makes the process stream an immediate candidate for the tubeside of a shell and tube heat exchanger. The cooling water is available at 80 °F and must be returned at a temperature no higher than 115 °F. The process engineer realizes that with the water flow being placed on the shellside, larger flowrates will enhance the heat transfer coefficient. The basis for the heat exchanger quotation was specified as follows:
| Tubeside | Shellside | |
| Flow Rate (GPM) | 500 | 1800 |
| Temperature In (°F) | 280 | 80 |
| Temperature Out (°F) | 150 | 92 |
| Allowable Pressure Drop (psig) | 15 | 15 |
According to the engineer's calculations, these basic parameters should provide a good shell and tube design with a minimum amount of C276 material (an expensive alloy). The completed specification sheet is forwarded to many manufacturers, including those that could easily quote plate and frame or another compact technology. A typical plate and frame unit designed to meet this specification would have about 650 ft2 of area compared to about 420 ft2 for a shell and tube exchanger. A plate and frame unit designed to the above specification is limited by the allowable pressure drop on the cooling water. If the cooling water flow is reduced to 655 GPM and the outlet water temperature allowed to rise to 115 °F, the plate and frame heat exchanger would contain about 185 ft2 of area. The unit is smaller, less expensive, and uses less water. The load being transferred to the cooling tower is the same.
The theory that applied to the shell and tube heat exchanger (increasing water flow will minimize heat transfer area), works in exactly the opposite direction for compact technologies. The larger water flow actually drives the cost of the unit upward. Rather than supplying a rigid specification to all heat exchanger manufacturers, the engineer should have explained his goal in regards to the process stream. Then he could have stated the following:
The process stream is to be cooled with cooling water. Up to 2000 GPM of water is available at 80 °F. The maximum return temperature is 115 °F.
This simple statement could result in vastly different configurations when compared with the designs that would result from the original specification.


FB